What is the AC Wattage Calculator?

This calculator finds the real power (in watts) consumed by a single-phase alternating-current load. In AC circuits, voltage and current are not always in phase, so the actual power delivered is the product of voltage, current and the power factor — the cosine of the phase angle between them. This tool is universal and works with any standard AC supply (120 V, 230 V, 240 V, etc.).

How to use it

Enter the supply voltage in volts, the current drawn in amperes, and the power factor (a number between 0 and 1). A purely resistive load like a heater has a power factor of 1; motors and electronics typically range from 0.7 to 0.95. The calculator returns the real power in watts and the apparent power in volt-amperes (VA).

The formula explained

The core equation is

P = V × I × \cos\varphi
where P is real power (W), V is RMS voltage, I is RMS current, and \cos\varphi is the power factor. Apparent power is simply S = V × I (in VA). Real power is what your appliance actually converts to useful work and what your energy meter bills you for.

Worked example

Suppose a motor runs on 230 V drawing 5 A with a power factor of 0.9. Real power =

230 × 5 × 0.9 = 1035\ W
The apparent power is 230 × 5 = 1150\ VA, showing the supply must be sized for more than the useful wattage.

Typical Power Factor Values by Load Type

Power factor (\cos\varphi) describes how effectively a load converts the supplied current into useful real power. Purely resistive loads have a power factor of 1.0, while motors and electronic loads draw additional reactive current that lowers the figure. The values below are typical operating ranges; the exact figure varies with load, age and design.

Load type Typical power factor Notes
Incandescent lamp / heater (resistive) 1.0 Purely resistive — watts equal volt-amperes.
LED lighting (with driver) 0.5 – 0.95 Quality drivers reach 0.9+; cheap units can be low.
Fluorescent lamp with magnetic ballast 0.5 – 0.6 Improves to ~0.95 with electronic ballast or correction.
Refrigerator / fridge-freezer 0.6 – 0.8 Compressor motor dominates at start-up.
Washing machine motor 0.5 – 0.7 Varies through wash and spin cycles.
Induction motor (single-phase) 0.7 – 0.85 Lower at part-load, higher near full load.
Computer / SMPS power supply 0.6 – 0.95 Units with active PFC reach 0.95–0.99.
Air conditioner 0.8 – 0.9 Inverter models with PFC sit at the high end.

Wattage Across Common Scenarios

Real power is found with P = V × I × \cos\varphi, while apparent power is simply S = V × I (in volt-amperes). The apparent power equals the real power only when the power factor is 1.0; the gap between them widens as the power factor falls. The table below works each case through both formulas.

Voltage (V) Current (A) Power factor Apparent power (VA) Real power (W)
230 5 0.9 1150 1035
120 10 1.0 1200 1200
240 8 0.8 1920 1536
230 3 0.7 690 483

Worked example for the first row: S = 230 × 5 = 1150\ VA and P = 230 × 5 × 0.9 = 1035\ W. The 115 VA difference is reactive power that circulates without doing useful work.

Key Terms Explained

Real power (P)
The actual power converted into useful work or heat, measured in watts (W). Given by P = V × I × \cos\varphi. This is what an energy meter bills and what does mechanical or thermal work.
Apparent power (S)
The product of RMS voltage and RMS current, measured in volt-amperes (VA): S = V × I. It sets the rating of cables, transformers and generators, since they must carry the full current regardless of power factor.
Reactive power (Q)
The power that oscillates between source and reactive components (inductors, capacitors) without being consumed, measured in volt-amperes reactive (VAR): Q = V × I × \sin\varphi. The three powers relate as S^2 = P^2 + Q^2.
Power factor (cos φ)
The dimensionless ratio of real to apparent power, PF = P / S = \cos\varphi, ranging from 0 to 1. A value of 1 means all current does useful work; lower values mean wasted capacity.
RMS voltage / current
The root-mean-square values of an AC waveform, in volts (V) and amperes (A). RMS is the equivalent DC value producing the same heating, and is the voltage/current normally quoted (e.g. 120 V, 230 V mains).
Phase angle (φ)
The angle in degrees (or radians) by which the current waveform lags or leads the voltage waveform. Its cosine is the power factor; \varphi = 0^\circ gives a unity power factor (purely resistive load).

使用注意事項與精準校對原則(6 大核心守則)

📐 1. 嚴格對齊輸入量綱與單位

輸入各項數值時請務必確認量綱(例如小時、天數、金額、百分比),避免單位不匹配引發推算偏差。

🔒 2. 純前端本機毫秒級隱私保障

所有計算邏輯 100% 在您的終端瀏覽器內完成,資料絕不上傳伺服器,嚴格守護商業與個人隱私。

📊 3. 符合公認學術與產業計算模型

演算法嚴格遵循國際通用數學公式與標準計算模型,經多重情境交叉核對,數值嚴密精確。

📋 4. 一鍵複製與免登入 PDF 匯出

支援一鍵複製推算結果字串至剪貼簿,亦可直接點擊列印按鈕輸出純淨 PDF 工作報表。

🔄 5. 多情景敏感度動態對比

建議針對極端值與多組預期情景分別試算,觀察輸出數據的波動區間,輔助做出更穩健的決策。

🛡️ 6. 專業諮詢與日常參考免責聲明

本工具運算結果供日常排程、學業研習與事前參考之用,如涉及重大法規或投資決策請諮詢持證專家。

常見問題 (FAQ)

What is power factor?
It is the ratio of real power to apparent power, between 0 and 1. A value of 1 means voltage and current are perfectly in phase.
What if I have a resistive load?
Use a power factor of 1, so the wattage simply equals volts × amps.
Does this work for three-phase systems?
No — for balanced three-phase, multiply by √3 \((P = \sqrt{3} \times V \times I \times \cos\varphi)\). This calculator is for single-phase loads.